Advanced search
Related Searches: Bluetooth, Virtual Reality, android, mtk, smart phone, smart watch, Keyboard, OPENBOX View all
Picture of EH9115 Series 1 Phase Low frequency UPS 2-15KVA

EH9115 Series 1 Phase Low frequency UPS 2-15KVA

SKU: FS00018878
Reproduction is welcome and allowed for free circulation only.
     
Application:

It is suitable in industrial equipment and instruments,armarium,computer network,elevator and the overall regulated power supply in small enterprise.Servers, Data centers, Sensitive electronic equipment, Telecom...

Manual Main Features:

reliable, filtered, stabilized and regulated sine wave output (double conversion on-line technology) with filters for atmospheric disturbance suppression

high reliability: full microprocessor control with no-break static and manual by-pass

high level diagnostics: states, measurements and alarms - available from the built-in LCD

power factor correction with sinusoidal input to ensure a low impact on the mains supply (UPS input power factor, close to 1) for the single-phase/single-phase series

very low noise level <40dB(A)

low power consumption (“Economy Mode”, Smart Active Mode, and Standby/Off Mode to increase efficiency up to 98%)

simple to install:

easy to position (integrated castors)

built-in automatic and manual battery test feature

auto restart on mains return (programmable - software or from the front panel)

back feed protection as standard: to avoid energy feeding back into the mains supply

integrated automatic and manual by-pass.

Specifications:

MODEL EH9115 2K EH9115 3K EH9115 6K EH9115 10K EH9115 15K
CAPACITY 2KVA/1.6KW 3KVA/2.4KW 6KVA/4.8KW 10KVA/8KW 15KVA/12KW
INPUT
Voltage Single phase 220Vac -20% +35%
Voltage Range -15% +25% or -30% + 40% (Input adding AVR function)
Input Frequency 50Hz or 60Hz +/- 5%
OUTPUT
AC Voltage Regulation Single phase 220Vac +/- 5% (adjustable)
Voltage regulation +/-1%
Frequency Range 50Hz or 60Hz
Frequency Stability +/- 0.5% (Free Running)
Power Factor 0.8
Transient Response +/- 3% (100% load variation)
Overload Capacity 120% load 30 seconds, >150% constant power.
Transfer Time(AC to DC) Zero
Waveform Sinewave THD < 3% at 0-100% linear load
Crest ratio 3:1
Efficiency (AC to AC) >85%
BATTERY
Battery Type Maintenance free lead-acid batteries
DC Voltage 48VDC 192VDC
Charger 5A charger build in ,option 10Acharge
PROTECTION
Battery Battery low shutdown and breaker
Overload protection 125% 30sec. switch to bypass line & automatic re-transfer
Short circuit protection Current Limited and cut-off and fuse and breaker
UPS Fault Bypass, load supplied from mains less than 2ms.
Cooling Force ventilation
PHYSICAL
Dimension, D X W X H (mm) 210x500x530 305x585x740/ 380x680x950
Net Weight (kgs) 52 58 62 95 214
OPERATING ENVIRONMENT
Humidity 20-90% non-condensing
Temperature 0-40 degree C; 32-104 degree F
Noise Level Less than 45dB(at 1 meter)
INTERFACE
Contact Closure Support MEGATEC RUPS UPS monitoring software/SNMP
RS-232 Support MEGATEC RUPSII / UPSilon 2000 monitoring software